Rational CombiMaster CM Manuel d'utilisateur Page 48

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 186
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 47
-48-
S
S
C
C
Mode: Wet heat (98-103°C (208-218°F),
set temperature)
Function step
Select Wet heat
(Temp 98-103°C (208-218°F))
Select time or core temperature
Close cabinet door
Check water level inside steam
generator
Preheat steam generator,
if B5 is below 85°C (185°F);
Timer starts after successful preheating
Steam production up to saturation in
cabinet
Adding of Hot Air from 70°C (158°F)
possible, if 70% humidity reached
Quenching (set to 70°C/158°F)
Responsible sensor
Reed switch S3
Level electrode S2 in-
side Steam Generator
Thermocouple B5 inside
Steam Generator
Logic on PCB
Pressure sensor P1
Thermocouple B4
rpm motor via BUS
Cabinet sensor B1
Thermocouple B2
Signal
Door open: 12VDC X27:(1-2)
Door closed: 0VDC X27:(1-2)
X12:(1-4) > 2VAC => no water
X12:(1-4) ~ 0VAC => water
SSR active: 12VDC X24:(1-2)+(5-6)
SSR not active: 0VDC X24:(1-2)+(5-6)
Gas unit: Bus signal
SSR active: 12VDC X24:(1-2)+(5-6)
SSR not active: 0VDC X24:(1-2)+(5-6)
Gas unit: Bus signal
SSR active: 12VDC X24:(7-8)+(3-4)
SSR not active: 0VDC X24:(7-8)+(3-4)
Gas unit: Bus signal
B2 above set Temp.: Y2 active
B2 below set Temp.: Y2 not active
Remark
Solenoid Y1 energizes when
no water, 230VAC, X19:(1-4)
Heating off,
if B5 > 180°C (356°F)
Blinking dot on timer display
Decision of Hot Air supply by
PCB logic
Y2 act.: 230VAC, X19:(2-5)
Y2 not act.: 0VAC, X19:(2-5)
1
2
3
4
5
6
7
8
9
Additional functions possible: 4 Fan speeds (Standard = Level 4), pulsed fan wheel,
½ Energy, HACCP output, ∆T
Note:
Steam heating only active when humidity fl ap (S4) is in closed position!
SCC Units: Sequence of Events